Mongolia hybrid solar and battery storage system wall layout with distribution boxes
MONGOLIA · SOLAR + BATTERY STORAGE PROJECT

Mongolia Solar + Battery Storage Distribution Box Project

Custom DC and AC distribution boxes for 30kW and 20kW hybrid solar + battery storage systems in Ulaanbaatar, Mongolia, built to the customer single-line diagram.

LocationUlaanbaatar, Mongolia
CompletionNovember 2026
Systems30kW + 20kW hybrid PV + BESS
TPKELE scopeDC & AC distribution boxes
PROJECT OVERVIEW

Distribution Boxes Built From the Customer Single-Line Diagram

The customer, a Mongolian system integrator, sent single-line diagrams for two hybrid systems: a 30kW system with three 10kW three-phase inverters and a 184.32kWh LFP battery bank, and a 20kW system with two inverters and 92.16kWh of storage.

TPKELE builds the distribution layer between the battery, inverters and loads: battery-side DC boxes with 300A DC MCCBs, and AC boxes with a 4P breaker and 4P surge protector on every inverter output. The inverters, batteries and PV modules are customer-supplied.

SYSTEM LAYOUT

Battery, Hybrid Inverters and Distribution Boxes on One Wall

Wall layout drawings from the customer. Each inverter output gets its own 4P breaker and SPD in the AC box, and the battery bank connects through the DC box.

30kW system wall layout with three hybrid inverters, AC box and DC box
30kW system: AC distribution box (left), three 10kW hybrid inverters, DC distribution box and battery cabinet (right).
20kW system wall layout with two hybrid inverters, AC box and DC box
20kW system: AC distribution box (left), two 10kW hybrid inverters, DC distribution box and battery cabinet (right).
DISTRIBUTION BOX CONTENTS

What Goes Into Each Box

Distribution box contents from the project bill of materials, followed by the customer-supplied system equipment for context.

DC-01 / DC-02 Battery-Side DC Distribution Box

2P 300A DC MCCB · 12× PG21 cable glands per box

Isolates and protects the 48V LFP battery bank on the DC side of the hybrid inverters.

AC-01 AC Distribution Box — 30kW system (11 sets)

3× 4P 25A AC MCB · 6× 2P 16A AC MCB · 3× 4P 20kA AC SPD · PE busbar · 6× PG21

One 4P breaker and one 4P SPD per inverter output, plus six 2P outgoing feeders, matching the customer single-line diagram.

AC-02 AC Distribution Box — 20kW system

2× 4P 25A AC MCB · 2× 4P 20kA AC SPD per box

The same per-inverter protection logic applied to the two-inverter system.

Hybrid Inverters

SUN-10K-SG05LP3-EU-SM2 · 10kW three-phase · 3 units (30kW) / 2 units (20kW)

Customer-supplied equipment shown in the single-line diagram.

Battery Storage

B-LFP48-300E · 12× 15.36kWh = 184.32kWh (30kW) / 6× 15.36kWh = 92.16kWh (20kW)

Customer-supplied equipment shown in the single-line diagram.

Solar PV Array

8× 630W modules per string · 4 strings per system shown

Customer-supplied equipment shown in the single-line diagram.

CUSTOMIZATION

What Was Built Specifically for This Project

✓

Built to the customer drawing

Box contents follow the customer single-line diagram: one 4P breaker and one 4P SPD per inverter output, plus the outgoing feeders.

✓

300A battery-side DC isolation

Each DC box carries a 2P 300A DC MCCB between the LFP battery bank and the hybrid inverters.

✓

Repeatable AC-01 build

The 30kW AC box is built as 11 identical sets, so every site gets the same layout, labeling and spare parts.

✓

Earthing included

AC-01 boxes include a PE busbar for SPD and enclosure earthing.

✓

Cable entry planned

PG21 cable glands are specified per box: 12 on each DC box, 6 on each AC-01 box.

✓

UV-printed front panel

Project panels are UV-printed with the box type and TPKELE branding.

UV-printed DC distribution box front panel with TPKELE branding
UV-printed front panel artwork for the DC distribution box.
TPKELE PRODUCT FIT

TPKELE Products and Services in This Project

Standard TPKELE breakers and surge protectors where the specification matches a product family, assembled into boxes built to the customer drawing.

TECHNICAL DETAILS

Box-by-Box Breakdown and Power Path

DC-01 / DC-02

2P 300A DC MCCB + 12× PG21 per box

AC-01 (30kW, 11 sets)

3× 4P 25A AC MCB + 6× 2P 16A AC MCB + 3× 4P 20kA AC SPD + PE busbar + 6× PG21

AC-02 (20kW)

2× 4P 25A AC MCB + 2× 4P 20kA AC SPD

Power path

PV strings + LFP battery → DC box → 10kW hybrid inverters → AC box (4P MCB + 4P SPD per inverter) → 2P 16A outgoing feeders