DC Surge Protection Guide

How to Select a DC SPD for PV Systems: Ucp, In, Imax and Up Explained in 2025

5 min read

This guide explains how a DC surge protective device works in photovoltaic and other DC distribution systems. It shows buyers and electrical contractors how to interpret Ucp, In, Imax, Up, pole configuration, installation position, and applicable standards before specifying a DC SPD.

Compliance note: DC SPDs for photovoltaic systems should be assessed against IEC 61643-31, IEC 60364-7-712, UL 1449, and the applicable AS/NZS 5033 requirements; European buyers should verify the applicable CE documentation, while Australian and New Zealand buyers should confirm RCM and local installation requirements. Buyers must verify the exact voltage rating, test classification, certification scope, and installation conditions for the specific model purchased.

Why DC Surge Protection Matters

PV strings and their long outdoor cable runs can experience transient overvoltages from nearby lightning strikes, even without a direct strike to the array. Switching operations and disturbances coupled through connected equipment can also produce short-duration voltage spikes in battery systems and other DC distribution circuits. These transients may stress inverter inputs, battery converters, charge controllers, and monitoring equipment beyond their insulation or impulse-withstand limits.

A DC surge protective device (SPD) limits transient voltage at its connection point by conducting surge current through a designated path when the voltage rises above its operating threshold. In PV installations, the relevant product standard is IEC 61643-31 for SPDs connected to the DC side of photovoltaic systems. Effective protection also depends on the installation position, conductor routing, bonding, and coordination with the equipment being protected.

Surge protection is not overcurrent protection
An SPD addresses short-duration overvoltage events; it does not replace a DC-rated fuse or circuit breaker for sustained overloads or short circuits. Any required SPD backup protection and disconnection arrangement must be checked against the specific SPD manufacturer's instructions and the applicable installation rules.

How a DC SPD Diverts Surge Energy

A DC surge protective device (SPD) uses voltage-dependent components, such as metal-oxide varistors or gas-discharge tubes, to limit a transient overvoltage. Under normal operating voltage, the device presents a high impedance and carries little current. When a surge drives the voltage above its operating threshold, the protective components conduct and divert surge current away from the protected equipment. In a PV installation, the discharge path depends on the SPD topology and may run from DC positive or negative to the protective earth (PE) bonding system.

  • Bond the SPD PE terminal to the installation's equipotential bonding system; the discharge path must be continuous and suitable for surge current.
  • Keep the conductors from the DC circuit to the SPD and from the SPD to PE as short and direct as practicable. Their inductance produces additional voltage during a fast surge, increasing the voltage seen by the equipment above the SPD's stated voltage protection level (Up).
  • Assess the complete earthing and bonding arrangement, including connection quality and conductor routing. A low earth-electrode resistance alone does not establish a low-impedance path for a fast transient.

The SPD's published Up is measured under specified test conditions; it is not a guarantee of the voltage at the inverter or other load. Lead length, bonding impedance and installation layout can raise the effective residual voltage at that equipment. For PV applications, check that the selected device is specified for the intended DC circuit and evaluated to IEC 61643-31, then confirm the permitted connection topology in the specific model's installation instructions.

Operating Principle Diagram
img-1

DC SPD Ratings Buyers Must Check

Review the SPD nameplate and datasheet as a set: voltage, discharge-current ratings, protection level, fault-current coordination, and environmental limits must suit the PV array and the installation. Confirm that the stated ratings apply to the relevant DC application and configuration, rather than inferring performance from a product category or a single headline value. For PV SPDs, check the manufacturer’s terminology and applicable product standard; requirements and test classifications can differ by device type and market.

UcpvMaximum continuous operating voltage for the PV SPD. It must be compatible with the array’s maximum open-circuit voltage at the lowest design temperature, including the system voltage basis specified by the manufacturer. Do not select from nominal DC voltage alone.
InNominal discharge current, usually an 8/20 μs impulse-current rating. It is a declared test rating, not a guarantee that the SPD will withstand repeated surges indefinitely. Compare the value and test basis stated in the datasheet.
ImaxMaximum discharge current, generally specified for an 8/20 μs impulse. It indicates a higher single-discharge capability than In under the declared test conditions; it should not be treated as the normal operating rating or as a substitute for checking In.
UpVoltage protection level: the declared limiting voltage under specified test conditions. Check that it is appropriate for the withstand voltage of the protected equipment and consider connection-lead effects, which can increase the voltage at the equipment terminals.
Short-circuit withstand and backup protectionConfirm the SPD’s short-circuit current rating or withstand declaration, the prospective fault current at its installation point, and any required upstream fuse or circuit breaker. Verify the specified backup protective device and coordination against the exact SPD datasheet; do not assume a generic DC fuse or breaker is suitable.
Pole configurationMatch the device arrangement to the PV earthing system, conductor layout, and protection scheme. Check which poles protect positive, negative, and, where applicable, the earth or functional-earth path; verify the manufacturer’s connection diagram and permitted system configuration.
Operating temperatureCheck the declared ambient operating range against the enclosure location and expected site conditions. High temperatures can affect service life and suitability; confirm any derating or mounting restrictions in the product documentation.
Replacement indicationCheck how end-of-life status is indicated, such as a visual status window or remote signalling contact, and whether the indication is available for the selected configuration. Confirm what replacement action the manufacturer requires when the device signals failure.
Quotation checkWhat to verifyWhy it matters
Voltage selectionUcpv versus maximum array open-circuit voltage at minimum design temperatureAvoids selecting a device whose continuous-voltage rating is below the array’s design voltage.
Surge ratingsIn and Imax values, impulse waveform, and the manufacturer’s stated test conditionsAllows like-for-like comparison without treating different ratings as interchangeable.
Equipment coordinationUp and the protected equipment’s impulse withstand level; account for connection layoutChecks whether the declared protection level is suitable at the equipment terminals.
Fault coordinationProspective short-circuit current, SPD withstand declaration, and specified backup protective deviceConfirms the assembly is suitable for the installation’s fault conditions.
Configuration and servicePole diagram, operating temperature range, and local or remote replacement indicationConfirms fit with the system topology, installation environment, and maintenance requirements.
Resolve rating ambiguities before approval
Ask the supplier to identify the applicable product standard and test classification, provide the connection diagram, and state the required backup protective device. Confirm rating definitions and configuration against the exact model documentation; where a value or test condition is not declared, treat it as requiring confirmation for the specific model.
Parameter Explainer
img-2

Type 1, Type 2 and Combined Protection

IEC 61643-31 classifies SPDs for photovoltaic installations by their tested protection function. Type 1 devices are intended to conduct partial lightning current where lightning current may enter the installation; Type 2 devices limit induced surges and switching transients. A combined Type 1+2 SPD is tested for both functions, but the correct selection still depends on the PV system layout, lightning protection measures, and the manufacturer's specified installation conditions.

Type 1Use where a direct lightning-current component may enter the PV DC circuit, such as when required by the lightning protection and separation-distance assessment.Tested with an impulse current waveform, typically 10/350 µs (Iimp).For PV arrays, application and connection must follow the system design and the SPD manufacturer's instructions.
Type 2Use for induced lightning surges and switching overvoltages where Type 1 capability is not required at that location.Tested with a nominal discharge current waveform of 8/20 µs (In); maximum discharge current Imax is also associated with Type 2 testing.Commonly installed at PV inverter DC inputs or in array-side distribution equipment, subject to the installation design.
Combined Type 1+2Use where both partial lightning-current capability and voltage-limiting protection are needed at one location.Tested for Type 1 and Type 2 functions, including 10/350 µs Iimp and 8/20 µs discharge-current tests as applicable to the device.Can simplify protection at a PV DC distribution point; verify coordination, backup protection, and suitability for the system voltage.
ArrangementLightning exposure and contextTest waveformTypical PV application
Type 1Partial lightning current may enter the circuit; selection is based on the lightning protection assessment and installation conditions.10/350 µs impulse current (Iimp)PV DC circuit requiring Type 1 protection under the project design; exact position and configuration depend on the installation.
Type 2Induced surges or switching transients; no Type 1 requirement at that point.8/20 µs nominal discharge current (In); Imax is specified for the devicePV array or inverter DC side, selected and positioned according to cable routing, equipment layout, and manufacturer instructions.
Type 1+2Both partial lightning-current exposure and induced or switching surges must be addressed at the same protection point.Type 1 and Type 2 tests, including 10/350 µs and 8/20 µs waveforms as applicablePV DC distribution point where a combined device is appropriate; confirm coordination with other SPDs and the inverter.
Selection check
Do not select by type alone. Confirm the applicable edition of IEC 61643-31, the PV system's maximum voltage and earthing arrangement, required protection at each location, and the SPD's declared ratings and installation instructions.
Comparison Infographic
img-3

Where to Install a DC SPD in a PV System

Install DC SPDs at the boundaries where surge exposure or cable length can create a significant voltage difference between equipment and the protective device. In a PV system, typical locations include the array-side DC combiner box and the inverter DC input. The required positions depend on the system layout, lightning protection measures, cable routing, and the installation rules applicable in the target market.

  • At the array boundary, place protection near the point where PV strings enter the DC collection or distribution equipment, especially where long outdoor cable runs increase exposure.
  • In the DC combiner box, protect the incoming string circuits and consider protection at the box output where the route to the inverter is long or passes through a separate protection zone.
  • At the inverter input, install an SPD close to the DC terminals when the inverter is remote from the array or combiner box. Follow the inverter manufacturer's instructions and the applicable PV installation standard.
  • Route SPD conductors directly and keep the total connection path between the live conductors, SPD, and PE as short as the equipment design allows. Long or looped leads add inductive voltage during a surge and can reduce the protection achieved at the equipment terminals.
  • Where protection is required at more than one location, coordinate devices as parallel protection zones. Check the manufacturer's coordination guidance, cable distance requirements, and ratings rather than assuming that two SPDs will share surge current evenly.

The SPD's backup overcurrent protection must also be coordinated with the DC circuit. Use only the fuse or DC MCB arrangements permitted by the SPD manufacturer, including the specified maximum backup fuse rating and short-circuit withstand conditions. Do not treat a general-purpose AC MCB as suitable for a PV DC circuit; verify DC voltage, polarity, interrupting capacity, and the device's intended application.

Verify the complete protection path
Before specifying the installation, confirm the SPD location, conductor route and length, earthing connection, and backup fuse or DC MCB against the system design and the relevant local requirements. Device-specific coordination and lead-length limits must be confirmed from the technical documentation for the selected SPD.
Application Diagram
img-4

Compliance and Project Verification

Check the requirements of the destination market and the specific PV installation before approving a DC SPD. A product standard establishes how the device is tested; an installation standard governs how protection is applied in the system. A claim of IEC compliance does not, by itself, establish a UL listing or compliance with Australian installation requirements. Verify all evidence against the exact model and configuration being supplied.

StandardRelevance to a PV DC SPDApproval check
IEC 61643-31Requirements and test methods for SPDs connected to the DC side of PV installations.Request test evidence covering the specified model and its declared PV ratings.
IEC 60364-7-712Installation requirements for solar photovoltaic power supply systems.Confirm that the proposed protection arrangement is consistent with the project design and applicable installation rules.
UL 1449US safety standard for surge protective devices.For US projects requiring a listed device, verify the listing, device type and DC/PV application against the exact model.
AS/NZS 5033Australian and New Zealand installation and safety requirements for PV arrays.Confirm the array-side SPD arrangement against the applicable project design and local requirements.
Model-specific datasheetRequest the complete part number, pole configuration, Ucp, In, Imax, Up, short-circuit withstand information and operating conditions.
Compliance evidenceRequest the applicable declaration of conformity and IEC 61643-31 test report; obtain a verifiable UL 1449 listing record where the project requires one.
Installation instructionsRequest the wiring diagram, terminal and conductor requirements, earthing instructions, and any specified backup overcurrent protection.
Project approval recordsRequest the approved single-line diagram and a schedule linking each proposed SPD model to its installation location and required standard.

Specify the Correct DC SPD

Before requesting a quotation, prepare a short specification based on the PV array, installation position, and destination market. Record the maximum expected DC voltage and the required Ucp, discharge-current ratings, Up, and pole configuration. For a PV-side SPD, request model-specific documentation against IEC 61643-31 rather than assuming that a product-family description establishes conformity for every variant. ([webstore.iec.ch](https://webstore.iec.ch/en/publication/26931?utm_source=openai))

PV DC surge protection

Review TPKELE DC SPDs

View the DC SPD product page, then submit your project requirements for model-level specifications and quotation support. Confirm ratings and documentation for the specific model offered. ([tpkele.com](https://www.tpkele.com/products/dc-spd))

View DC SPD Products
Selection Flowchart
img-5

Technical disclaimer: This guide provides general technical principles for product selection and application. Final specifications must be determined by a qualified electrical engineer based on actual site conditions, local electrical codes, load characteristics, and installation environment. TPKELE is not liable for damages resulting from improper product selection, installation, or use. Always verify compliance with applicable standards (IEC, UL, AS/NZS, etc.) and consult local authorities before installation.

Нужна помощь по этому семейству продуктов?

Отправьте список проектов — ответим в течение одного рабочего дня.